Cable Calc Formula [exclusive] ✦ Trusted

[ S = \fracI_sc \cdot \sqrtt\sqrt\epsilon \cdot \frac1k ] In non-linear loads, harmonic currents cause extra (I^2R) losses. The effective RMS current is:

And always, always derate for grouping.

(IEC 60364-5-52): Base cable 120 mm² Cu XLPE → 380 A in free air. Derate: (k_amb = 0.87), (k_group = 0.8) → (380 \times 0.87 \times 0.8 = 264 A) → too low. Try 185 mm² → base 500 A → derated = (500 \times 0.696 = 348 A) — acceptable. cable calc formula